Publication 1763-UM001D-EN-P - March 2011
Using the LCD 115
5. We will change the data value of the B3:0/0 bit to OFF (0).
First, press OK to select the displayed address and move the cursor to
the data value position. Then, “ON” will be flashing, which means the
cursor is at the data value position.
6. Press the Down key. Then, the data value will be represented as “OFF”.
Note that “OFF” is still flashing, which means the cursor is still at the
data value position.
7. Press OK to apply the changes. Then, the new value OFF (0) is applied.
Note that the target bit, “0/0” in this example, is flashing. The cursor is
moved automatically to the target bit position.
You can identify this change of data value is reflected to your RSLogix
500 programming software.