Rockwell-automation 1763 MicroLogix 1100 Programmable Controllers User Manual de usuario Pagina 158

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 157
Publication 1763-UM001D-EN-P - March 2011
156 Specifications
MicroLogix 1100 DC Input Power Requirements for 1763-L16BBB Unit
ESD immunity EN 61000-4-2
4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity EN 61000-4-3
10V/m, 26…1000 MHz (alternatively, 80…1000 MHz),
80% amplitude modulation, +900 MHz keyed carrier
Fast transient immunity EN 61000-4-4
2 kV, 5 kHz
communications cable such as EtherNet, RS-232, and RS-485: 1 kV, 5 kHz
Surge transient immunity EN 61000-4-5
Unshielded communications cable: 2 kV CM (common mode), 1 kV DM (differential mode)
Shielded communications cable: 1 kV galvanic gun
I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
AC Power Supply Input: 4 kV CM (common mode), 2 kV DM (differential mode)
DC Power Supply Input: 500V CM (common mode), 500V DM (differential mode)
AC/DC Auxiliary Output: 500V CM (common mode), 500V DM (differential mode)
Conducted RF immunity EN 61000-4-6
10V, 150 kHz…80 MHz
Conducted emissions EN 55011
AC Power Supply Input: 150 kHz…30 MHz
Radiated emissions EN 55011
30…1000 MHz
Line related tests EN 61000-4-11
AC Power Supply Input:
voltage drop: -30% for 10 ms, -60% for 100 ms
voltage interrupt: at voltage greater than -95% for 5 sec.
voltage fluctuation: +10% for 15 minutes, -10% for 15 minutes
DC Power Supply Input:
voltage fluctuation: +20% for 15 minutes, -20% for 15 minutes
General Specifications
Description 1763-
L16AWA L16BWA L16BBB L16DWD
4 8 121620
28
21
14
7
1763-L16BBB and 1763-L16DWD Typical Power Requirements
Calculated Load power (Watts)
In
p
u
t
P
o
w
e
r
R
e
q
u
ir
e
d
a
t
2
4
V
D
C
(W
a
t
t
s
)
0
Vista de pagina 157