Rockwell-automation 1763 MicroLogix 1100 Programmable Controllers User Manual de usuario Pagina 40

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 39
Publication 1763-UM001D-EN-P - March 2011
38 Installing Your Controller
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or
1492-EAH35) for vibration or shock environments. The following illustration
shows the location of the end anchors.
Panel Mounting
Use the dimensional template shown below to mount the module. The
preferred mounting method is to use two M4 or #8 panhead screws per
module. Mounting screws are required on every module.
TIP
1762 expansion I/O must be mounted horizontally as
illustrated.
TIP
For environments with greater vibration and shock
concerns, use the panel mounting method described below,
instead of DIN rail mounting.
End Anchor
End Anchor
90
(3.54)
100
(3.94)
40.4
(1.59)
A
40.4
(1.59)
14.5
(0.57)
MicroLogix
1100
1762 I/O
1762 I/O
1762 I/O
For more than 2 modules: (number of modules - 1) x 40 mm (1.59 in.)
NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.4 mm (0.016 in.).
A = 95 mm (3.740 in.)
1763-L16AWA, 1763-L16BWA, 1763-L16BBB
Vista de pagina 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 255 256

Comentarios a estos manuales