Publication 1763-UM001D-EN-P - March 2011
158 Specifications
Analog Input Specifications
Description 1763-L16AWA, -L16BWA, -L16BBB, -L16DWD
Voltage input range 0…10.0V DC - 1 LSB
Type of data 10-bit unsigned integer
Input coding (0...10.0V DC - 1 LSB) 0…+1,023
Voltage input impedance 210 kΩ
Input resolution 10 bit
Non-linearity ±1.0% of full scale
Overall accuracy
-20…65 °C (-4…149 °F)
±1.0% of full scale
Voltage input overvoltage protection 10.5V DC
Field wiring to logic isolation Non-isolated with logic
Output Specifications - General
Description 1763-
L16AWA, L16BWA, L16DWD L16BBB
Relay and FET Outputs
Maximum controlled load 1,440 VA 1,440 VA
Maximum continuous current
Current per group common
(1)
5A/3A 5A/3A
Current per controller at 150V max For UL 508, 30 A or total of per-point loads, whichever is less
For UL 1604, 18 A or total of per-point loads, whichever is less
at 240V max For UL 508, 20 A or total of per-point loads, whichever is less
For UL 1604, 18 A or total of per-point loads, whichever is less
Relay Outputs
Turn on time/Turn off time
10 ms (minimum)
(2)
Relay life - Electrical For Hazardous Locations Applications (Class I, Division 2, Groups A, B, C, D):
150 x 10
3
operations min. (at 3 A, 30V DC);
370 x 10
3
operations min. (at 3 A, 250V AC);
For Ordinary (Non-Hazardous) Locations only:
50 x 10
3
operations min. (at 5 A, 30V DC);
170 x 10
3
operations min. (at 5 A, 250V AC);
Load current 10 mA (min.)
(1) 5A for UL 508
3A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D
(2) scan time dependent