Publication 1763-UM001D-EN-P - March 2011
174 Specifications
Input Specifications 1762-IR4
Specification 1762-IR4
Input types 100 Ω Platinum 385
200 Ω Platinum 385
500 Ω Platinum 385
1,000 Ω Platinum 385
100 Ω Platinum 3916
200 Ω Platinum 3916
500 Ω Platinum 3916
1,000 Ω Platinum 3916
10 Ω Copper 426
120 Ω Nickel 672
120 Ω Nickel 618
604 Ω Nickel-Iron 518
0…150 Ω
0…500 Ω
0…1,000 Ω
0…3,000 Ω
Heat dissipation 1.5 Total Watts (The Watts per point, plus the minimum Watts, with all points enabled.)
Normal mode rejection ratio 70 dB minimum at 50 Hz with the 10 or 50 Hz filter selected
70 dB minimum at 60 Hz with the 10 or 60 Hz filter selected
Typical accuracy
[Autocalibration enabled] at 25 ° C (77 °F)
ambient with module operating
temperature at 25 °C (77 °F)
(1)
±0.5 °C (°F) for Pt 385
±0.4 °C (°F) for Pt 3916
±0.2 °C (°F) for Ni
±0.3 °C (°F) for NiFe
±0.6 °C (°F) for Cu
±0.15 Ω for 150 Ω range
±0.5 Ω for 500 Ω range
±1.0 Ω for 1,000 Ω range
±1.5 Ω for 3,000 Ω range
Typical accuracy
[Autocalibration enabled] at 0…55 °C
(32…131 °F)
(1)
±0.9 °C (°F) for Pt 385
±0.8 °C (°F) for Pt 3916
±0.4 °C (°F) for Ni
±0.5 °C (°F) for NiFe
±1.1 °C (°F) for Cu
±0.25 Ω for 150 Ω range
±0.8 Ω for 500 Ω range
±1.5 Ω for 1,000 Ω range
±2.5 Ω for 3,000 Ω range
Accuracy drift at 0…55 ° C (32…131 °F) ±0.026 °C/°C (0.026 °F/°F) for Pt 385
±0.023 °C/°C (0.023 °F/°F) for Pt
3916
±0.012 °C/°C (0.012 °F/°F) for Ni
±0.015 °C/°C (0.015 °F/°F) for NiFe
±0.032 °C/°C (0.032 °F/°F) for Cu
±0.007 Ω/°C (0.012 Ω/°F) for 150 Ω range
±0.023 Ω/°C (0.041 Ω/°F) for 500 Ω range
±0.043 Ω/°C (0.077 Ω/°F) for 1,000 Ω range
±0.07 2Ω/°C (0.130 Ω/°F) for 3,000 Ω range
Excitation current source 0.5 mA and 1.0 mA selectable per channel
Open-circuit detection time
(2)
6…1212 ms
Input channel configuration Via configuration software screen or the user program (by writing a unique bit pattern into the
module’s configuration file). Refer to your controller’s user manual to determine if user
program configuration is supported.
Calibration The module performs autocalibration on channel enable and on a configuration change
between channels. You can also program the module to calibrate every five minutes.
Maximum overload at input terminals ±35V DC continuous