Rockwell-automation 1763 MicroLogix 1100 Programmable Controllers User Manual de usuario Pagina 153

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 152
Publication 1763-UM001D-EN-P - March 2011
Online Editing 151
Interval be increased from the default of 1.25 seconds to 8 seconds as shown
in the following figure.
A Download Before Starting Online Edit
At least one download is required before starting online edit.
If you are using a MicroLogix 1100 from out-of-box state or after clear
processor memory or firmware upgrade, at least one download is required
before starting online edits. If not, the following error occurs and
programming software will go offline due to default image mismatch between
programming software (RSLogix500) and the MicroLogix 1100. You can also
see the fault code 1Fh which is a user defined fault code.
In order to prevent this error, a user needs to download the program to the
MicroLogix 1100, although the program is empty.
Vista de pagina 152
1 2 ... 148 149 150 151 152 153 154 155 156 157 158 ... 255 256

Comentarios a estos manuales

Sin comentarios