Rockwell-automation 1763 MicroLogix 1100 Programmable Controllers User Manual de usuario Pagina 88

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 87
Publication 1763-UM001D-EN-P - March 2011
86 Communication Connections
network to 2438 m (8000 ft). For additional information on connections using
the AIC+, refer to the Advanced Interface Converter (AIC+) User Manual,
publication 1761-6.4.
When cutting cable segments, make them long enough to route them from one
AIC+ to the next, with sufficient slack to prevent strain on the connector.
Allow enough extra cable to prevent chafing and kinking in the cable.
Use these instructions for wiring the Belden #3106A or #9842 cable. (See
Cable Selection Guide on page 90 if you are using standard Allen-Bradley
cables.)
Connecting the Communication Cable to the DH-485 Connector
Single Cable Connection
When connecting a single cable to the DH-485 connector, use the following
diagram.
TIP
A daisy-chained network is recommended. Do not
make the incorrect connection shown below:
Belden #3106A
or #9842
Belden #3106A or
#9842
Belden #3106A or
#9842
Connector
Connector
Connector
Incorrect
Orange with White Stripes
White with Orange Stripes
Shrink Tubing Recommended
Blue (#3106A) or
Blue with White
Stripes (#9842)
Drain Wire
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
Vista de pagina 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 255 256

Comentarios a estos manuales

Sin comentarios