Specifications 171
Analog Modules
Common Specifications
Specification 1762-IF2OF2, 1762-IF4, 1762-IR4, 1762-IT4 and 1762-OF4
Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width)
height including mounting tabs is 4.33 in.
Temperature, storage -40 °C…85 °C (-40 °F…185 °F)
Temperature, operating
-20 °C…65 °C (-4 °F…149 °F)
(1)
Operating humidity 5%…95% non-condensing
Operating altitude 2000 meters (6561 feet)
Vibration Operating: 10…500 Hz, 5 g, 0.030 in. max. peak-to-peak
Shock Operating: 30 g
Module power LED On: indicates power is applied.
Recommended cable Belden 8761 (shielded)
(For 1762-IT4, Shielded thermocouple extension wire for the specific type of thermocouple you are
using. Follow thermocouple manufacturer’s recommendations.)
Agency certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts (1762-IR4 and 1762-IT4)
Hazardous environment class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Noise immunity NEMA standard ICS 2-230
Radiated and conducted emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD immunity (IEC1000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated immunity (IEC1000-4-3) 10 V/m, 80…1,000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
Fast transient burst (IEC1000-4-4) 2 kV, 5 kHz
Surge immunity (IEC1000-4-5) 1 kV galvanic gun
Conducted immunity (IEC1000-4-6)
10V, 0.15…80 MHz
(2)
(3)
(1) For module-specific operating temperature range, refer to the Installation Instructions for the specific module.
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.
(3) For grounded thermocouples, the 10V level is reduced to 3V.