Publication 1763-UM001D-EN-P - March 2011
162 Specifications
Working Voltage (1763-L16BWA)
Description 1763-L16BWA
Power supply input to backplane isolation Verified by one of the following dielectric tests:1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (IEC Class 2 reinforced insulation)
Input group to backplane isolation and
input group to input group isolation
Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s
75V DC Working Voltage (IEC Class 2 reinforced insulation)
Output group to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (IEC Class 2 reinforced insulation).
Output group to output group isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)
Working Voltage (1763-L16BBB)
Description 1762-L16BBB
Input group to backplane isolation and
input group to input group isolation
Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s
75V DC Working Voltage (IEC Class 2 reinforced insulation)
FET output group to backplane isolation Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s
75V DC Working Voltage (IEC Class 2 reinforced insulation)
Relay output group to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (IEC Class 2 reinforced insulation).
Relay output group to relay output group
and FET output group isolation
Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)
Working Voltage (1763-L16DWD)
Description 1763-L16BWA
Input group to backplane isolation and
input group to input group isolation
Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s
75V DC Working Voltage (IEC Class 2 reinforced insulation)
Output group to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (IEC Class 2 reinforced insulation).
Output group to output group isolation Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s
265V
AC
Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)