3-4 Configuring the Adapter
4. Interbus requires the network I/O mapping to be configured first in
the adapter. CMD software will read this configuration online when
it is configuring the scanner.
Process Input Data Description (PIDD) words map input data on the
network (data seen as inputs to the scanner and controller program).
Example input data includes Logic Status, Feedback and Datalinks
(Datalink x1 Out). Up to 9 words of input data can be mapped.
Process Output Data Description (PODD) words map output data on
the network (data sent as outputs from the scanner and controller
program). Example output data includes Logic Command, Reference
and Datalinks (Datalink x1 In). Up to 9 words of output data can be
mapped.
The following indexes are used to select the I/O data:
Table 3.1 PIDD/PODD Indexes
Value
(Hex)
Value
(Dec)
Selects
2F9A 12186 Logic Status
2F9B 12187 Feedback
2FA4 12196 Datalink A1 Out
2FA5 12197 Datalink A2 Out
2FA6 12198 Datalink B1 Out
2FA7 12199 Datalink B2 Out
2FA8 12200 Datalink C1 Out
2FA9 12201 Datalink C2 Out
2FAA 12202 Datalink D1 Out
2FAB 12203 Datalink D2 Out
Value
(Hex)
Value
(Dec)
Selects
2F98 12184 Logic Command
2F99 12185 Reference
2F9C 12188 Datalink A1 In
2F9D 12189 Datalink A2 In
2F9E 12190 Datalink B1 In
2F9F 12191 Datalink B2 In
2FA0 12192 Datalink C1 In
2FA1 12193 Datalink C2 In
2FA2 12194 Datalink D1 In
2FA3 12195 Datalink D2 In
Input
Output
20COMM-UM007A-EN-P.book Page 4 Tuesday, January 22, 2002 10:52 AM