5-8 Using I/O Messaging
Figure 5.3 Example SLC Ladder Logic - Main Program
SLC Ladder Logic Example - Main Program
Execute LAD 3 - Station 1.0 Drive Logic (Logic Command / Status, Reference / Feedback and Datalinks).
Execute LAD 4 - Station 2.0 Drive Logic (Logic Command / Status, Reference / Feedback and Datalinks).
Can Read OR Write at any one time. B3:47/0 will be turned off by the subroutine when the reading is complete and signals that
Can only Write OR Read at any one time. B3:47/10 will be turned off by the subroutine when the writing is complete and
The following rung performs power-up initialization of the PCP Read and PCP Write routines.
0000
S:1
15
First Pass
U
B3:47
0
Execute
PCP Read
Subroutine
U
B3:47
1
PCP Read
Routine
1-shot
U
B3:47
2
PCP Read
Reply Msg
1-Shot
U
B3:47
10
Execute
PCP Write
Subroutine
U
B3:47
11
PCP Write
Routine
1-shot
U
B3:47
12
PCP Write
Reply Msg
1-Shot
0001
JSR
Jump To Subroutine
SBR File Number U:3
JSR
0002
JSR
Jump To Subroutine
SBR File Number U:4
JSR
Execute LAD 5 - PCP Read Subroutine (Explicit Messaging)
another read (or write) cycle can take place.
0003
B3:47
0
Execute
PCP Read
Subroutine
B3:47
10
Execute
PCP Write
Subroutine
JSR
Jump To Subroutine
SBR File Number U:5
JSR
Execute LAD 6 - PCP Write Subroutine (Explicit Messaging)
signals that another write (or read) cycle can take place.
0004
B3:47
0
Execute
PCP Read
Subroutine
B3:47
10
Execute
PCP Write
Subroutine
JSR
Jump To Subroutine
SBR File Number U:6
JSR
0005
END