11Ć3
Release
ON LINE direct C: \LIB\SYS\RACK
Auto RunF3ăExit Direct Set Access Userlist
F1ăHelp Baud RateNetwork
Config
NORMAL Keysw Program Access Task Auto Run DISABLED
Slot Task ăăăă Type ăăPri R C M A Status Slot Task ăăăăăăăăăType Pri R C M A Status
"1 BASTEST Bas 4 R C RUN
1
BASTEST1 Bas 4 Stop
1
BASTEST2 Bas
4
C Stop
1
BASTEST3 Bas 5 R Stop
1
BASTEST4 Bas 6 C Stop
1
BASTEST5 Bas 7
Stop
1
BASTEST6 Bas 8 R C Stop
1
BASTEST7 Bas 9 Stop
1
BASTEST8 Bas 10
C Stop
1
BASTEST9 Bas 4 R Stop
1
INITDACS Bas 11 Stop
1
PCCOILS PC 11R Stop
1
PCTESTV5 PC 11 R C Stop
Figure
11.2 Ć
ON LINE Menu Display with Task Running
The top status line displays general information about the rack. The
Config" field shows whether the NORMAL or DEBUG version of the
rack configuration has been loaded to the rack. If the rack
configuration has not been loaded, NONE" wll be displayed. The
keyswitch position, Program in this case, is shown in the Keysw"
field. The Forced" field, when shown, indicates whether there are
any forced variables in the rack. See 18.5 for more information on
forcing.
The user's access level is displayed in the field Access" as None,
Data, Rack, Locked, or, as shown here, Task". Auto Run" is either
enabled" or as shown here, Disabled". See 12.4 for more
information about AUTOĆRUN.
The second status line displays specific information about tasks in
the rack. Slot" denotes the AutoMax Processor or UDC module on
which the task is running. Task" is the name of the task and Type"
denotes the programming language (.BLK, .BAS, or .PC).
Pri" is the task's priority as defined in the configuration for the rack.
The priority ranges from 4 (highest) to 11 (lowest). UDC tasks do not
display a priority
.
A" is displayed for Drive A tasks; B" is displayed
for Drive B tasks. See Appendix C for more information on task
priority. The field R" will show an R if the task is reconstructible. See
8.1.1 for more information about the /Reconstruct option used in
compiling tasks.