BĆ5Processor Module Error and Status Codes
AutoMax DriveĆRelated Error Codes
The following error codes indicate a power circuit or external drive system fault.
They apply only to systems that incorporate DCS 5000 microĆregulators. After
correcting the problem, reset the Processor module by cycling power and
reĆloading the configuration task and application tasks to clear the error code.
Note that these error codes also appear in the Error Log for the Processor.
80 Instantaneous overcurrent fault
Ć armature current exceeded IOC_THRESH
value in CML task
81 Line sync loss fault
82 Tach loss fault
Ć 40% armature phase angle with less than 5% tach
feedback
83 Overspeed/overvoltage fault
Ć CML task OSV_FDBK exceeded OSV_THRESH
number
84 Hardware overspeed fault
Ć drive analog module potentiometer setting
exceeded by input voltage
85 External IET fault
Ć external fault input triggered
86 Phase rotation fault
Ć incorrect phasing
87 Shorted SCR detected in power module
Corrective action: troubleshoot power circuit and external drive system. These
errors do not cause a Stop All and do not require reĆloading the configuration or
application tasks.
Configuration Error Codes
The following error codes usually indicate a discrepancy between the actual
hardware configuration and the I/O definitions in the configuration for the rack.
E0 TASK specified in configuration uninstalled,
at wrong priority, of wrong type, on wrong
Processor module; wrong spelling of TASK
E1 Invalid configuration, configuration not successfully downloaded.
E2 I/O referenced in configuration is missing.
E3 I/O referenced in configuration is missing. Invalid configuration,
configuration not successfully downloaded.
E4 Error building task, insufficient memory in Processor Module.
Invalid configuration, configuration not successfully downloaded.
E5 Error building task, insufficient memory in Processor Module.
Invalid configuration, configuration not successfully downloaded.
E6 I/O referenced in configurations is missing. Error building task,
insufficient memory in Processor Module.
E7 Invalid configuration, configuration not successfully downloaded.
I/O referenced in configuration is missing. Invalid configuration,
configuration not successfully downloaded.
E8 Error installing application task, common symbol could not be
resolved, insufficient memory in Processor Module.
E9 Error installing application task, common symbol could not be
resolved, insufficient memory in Processor Module. Invalid
configuration, configuration not successfully downloaded.