BĆ6 AutoMax Programming Executive Version 3.x
EA Error installing application task, common symbol could not be
resolved, insufficient memory in Processor Module. I/O referenced
in configuration is missing.
Eb Error installing application task, common symbol could not be
resolved, insufficient memory in Processor Module. I/O referenced
in configuration is missing. Invalid configuration, configuration not
successfully downloaded.
EC Error building task; and error installing application task, common
symbol could not be resolved, insufficient memory in Processor
Module.
Ed Error building task; and error installing application task, common
symbol could not be resolved, insufficient memory in Processor
Module. Invalid configuration not successfully downloaded.
EE Error building task; and error installing application task, common
symbol could not be resolved, insufficient memory in Processor
Module. I/O referenced in configuration is missing.
EF Common variable forced by another Processor Module.
Corrective action: verify that the configuration correctly describes the physical
configuration of the system and the tasks installed on the Processor module(s).
Reset by cycling power and reĆloading the configuration and application tasks.
For error code EF, unĆforce the variable and do a STOP ALL from the AutoMax
ON LINE PROGRAMMING menu.

The following error codes usually indicate that the runbase is not functioning
correctly.
If any of these error codes appears, the configuration and all application
tasks are deleted from the Processor module.
F0ĆF9 Fatal error
FAĆFF Fatal error
Corrective action: cycle power. ReĆload the configuration and all application
tasks. Replace the Processor module.


The following codes signify a particular condition, not necessarily an error.
dd This Processor module has successfully
completed powerĆup diagnostics and is waiting for
other Processor modules to complete their
diagnostics
L0 The runbase needs to be loaded onto the rack
b0 Rack configuration is being validated
d0 Application task installation in progress
d1 Waiting on synchronizing event (in a rack with
multiple Processors)
d2 Waiting on mutual exclusion lock (in a rack with
multiple Processors)
Corrective action for b0 and d0 that do not change or disappear: reĆload
configuration and application tasks.