A-2 Specifications
NOTE: In order to remain CE and CTick compliant, the SCANport
cable length may not exceed 30 m (98.4 ft.).
NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in
which case supplementary mitigation measures may be required.
Environmental
Temperature
Operating
Storage
-10 to 50° C (14 to 149° F)
-40 to 85° C (-40 to 185° F)
Relative Humidity 5 to 95% non-condensing
Atmosphere Important: Module must not be installed in an area where
the ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the module is not going to be installed for a
period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
Shock
Operational
Non-Operational
30g, 11 ms (DIN Rail Mount)
50g, 11 ms (Panel Mount)
30g, 11 ms (DIN Rail Mount)
50g, 11 ms (Panel Mount)
Vibration
Operational
Non-Operational
2.5g, 5 to 2000 Hz
5.0g, 5 to 2000 Hz
Regulatory Compliance
UL UL508C
cUL CAN / CSA C22.2 No. 14-M91
CE EN50178 and EN61800-3
CTick EN61800-3