Troubleshooting 7-5
Net B Status Indicator
Status Cause Corrective Action
Off The module is not powered
or is not transmitting on the
EtherNet/IP network.
If Net A is off:
Securely connect the module to the drive using a
1202-Cxx Communication cable.
Securely connect the Ethernet cable to the Ethernet
connector.
Set a unique IP address using a BOOTP server or
by disabling BOOTP and using parameters.
If Net A is solid red:
Configure the module to use a unique IP address
and cycle power.
If Net A is flashing red/green or red:
Check the IP address in the module and scanner.
Ping the module.
Normal condition if the module is idle.
Flashing Green The module is transmitting
on the EtherNet/IP
network.
No action required.