C-2 EtherNet/IP Objects
Class Code
Instances
The number of instances depends on the number of components in the
device connected to the module. This number of components can be read
in Instance 0, Attribute 2.
Class Attributes
Instance Attributes
Identity Object
Hexadecimal Decimal
0x01 1
Instance Description
0Class
1 Entire device (SCANport host)
2 (n + 1) n firmware components of drive
(n + 2) 1203-EN1
(n + 3) 1203-EN1 application firmware
(n + 4) 1203-EN1 boot firmware
Attribute
ID
Access
Rule Name Data Type Description
2 Get Max Instance UINT Total number of instances
Attribute
ID
Access
Rule Name Data Type Description
1 Get Vendor ID UINT 1 = Allen-Bradley
2 Get Device Type UINT 128
3 Get Product Code UINT Number identifying product
name and rating
4 Get Revision:
Major
Minor
STRUCT of:
USINT
USINT
Value varies
Value varies
5 Get Status WORD Bit 0 = Owned
Bit 2 = Configured
Bit 10 = Recoverable fault
Bit 11 = Unrecoverable fault
6 Get Serial Number UDINT Unique 32-bit number
7 Get Product Name SHORT_
STRING Product name and rating