Module Parameters B-9
57 [Peer Inp Enable]
Determines if Peer I/O input is on or off.
Default: 0 = Off
Values: 0 = Off
1 = On
Type: Read/Write
Reset Required: No
58 [Peer Inp Status]
Displays the status of the consumed peer input
connection.
Default: 0 = Off
Values: 0 = Off
1 = Waiting
2 = Running
3 = Faulted
Type: Read Only
59
60
[Peer A Output]
[Peer B Output]
Selects the source of the Peer I/O output data.
The module transmits this data to the network.
Important: Changes to these parameters are
ignored when Parameter 61 - [Peer Out Enable] is
On.
Default: 0 = Off
Values: 0 = Off
1 = Cmd/Ref
2 = Datalink A Input
3 = Datalink B Input
4 = Datalink C Input
5 = Datalink D Input
6 = Datalink A Output
7 = Datalink B Output
8 = Datalink C Output
9 = Datalink D Output
Type: Read/Write
Reset Required: No
61 [Peer Out Enable]
Determines if Peer I/O output is on or off.
Default: 0 = Off
Values: 0 = Off
1 = On
Type: Read/Write
Reset Required: No
62 [Peer Out Time]
Determines the minimum time that a module will
wait when transmitting data to a peer.
Important: Changes to these parameters are
ignored when Parameter 61 - [Peer Out Enable] is
On.
Default: 10.00 Seconds
Minimum: 0.01 Seconds
Maximum: 10.00 Seconds
Type: Read/Write
Reset Required: No
63 [Peer Out Skip]
Determines the maximum time that a module will
wait when transmitting data to a peer. The value of
Parameter 62 - [Peer Out Time] is multiplied by the
value of this parameter to set the time.
Important: Changes to these parameters are
ignored when Parameter 61 - [Peer Out Enable] is
On.
Default: 1
Minimum: 1
Maximum: 16
Type: Read/Write
Reset Required: No
64 [Web Enable]
Displays the setting of the Web Pages Switch
(SW2) on the module when the module was last
reset.
Default: 0 = Disabled
Minimum: 0 = Disabled
Maximum: 1 = Enabled
Type: Read Only
Parameter
No. Name and Description Details