Rockwell-automation 1203-EN1 EtherNet/IP-to-SCANport Module Manual de usuario Pagina 36

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 186
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 35
3-10 Configuring the Module
4. Reset the module. See Resetting the Module section in this chapter.
The module is ready to receive I/O from the master (i.e., scanner). You
must now configure the scanner to recognize and transmit I/O to the
module. Refer to Chapter 4
, Configuring the Scanner or Bridge.
To set a module to transmit Peer-to-Peer data
1. Verify that Parameter 61 - [Peer Out Enable] is set to Off. This
parameter must be Off while you configure peer output parameters.
2. Select the source of the data to output to the network in Parameter
59 - [Peer A Output].
3. If desired, select an additional source of the data to output to the
network in Parameter 60 - [Peer B Output].
4. Set Parameters 62 - [Peer Out Time] and 63 - [Peer Out Skip] to
establish the minimum and maximum intervals between Peer
messages. Because the module transmits Peer messages when a
change-of-state condition occurs, minimum and maximum intervals
are required.
The minimum interval ensures that the module does not transmit
messages on the network too often, thus minimizing network
traffic. It is set in Parameter 62 - [Peer Out Time]. The default
is 10.00 seconds.
Table 3.F Parameter 61 - [Peer Out Enable] Setup Values
Value Setting
0 Off (Default)
1On
Table 3.G Parameter 59 - [Peer A Output] Setup Values
Value Description
0 Off (Default)
1 Logic Command/Reference
2 - 5 Datalink A, B, C, or D Input
6 - 9 Datalink A, B, C, or D Output
Table 3.H Parameter 60 - [Peer B Output] Setup Values
Value Description
0 Off (Default)
1 Logic Command/Reference
2 - 5 Datalink A, B, C, or D Input
6 - 9 Datalink A, B, C, or D Output
Vista de pagina 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 185 186

Comentarios a estos manuales

Sin comentarios