Troubleshooting 7-3
MOD Status Indicator
Status Cause Corrective Action
Off The module is not powered. Securely connect the module to the drive using a
1202-Cxx Communication cable.
Apply power to the module.
Flashing Red The module has failed the
firmware test.
The module is being flash
upgraded.
Clear faults in the module.
Cycle power to the drive and/or module.
If cycling power does not correct the problem, the
parameter settings may have been corrupted.
Reset defaults and reconfigure the module.
If resetting defaults does not correct the problem,
flash the module with the latest firmware release.
Solid Red The module has failed the
hardware test.
Cycle power to the module.
Replace the module.
Flashing Green The module is operational,
but is not transferring I/O
data.
Place the controller in RUN mode.
Program the controller to recognize and transmit
I/O to the module.
Configure the module for the program in the
controller.
Normal behavior if no SCANport I/O is enabled.
Solid Green The module is operational
and transferring I/O data.
No action required.
Flashing Red/
Green
The module is in boot mode. Flash the module with the latest firmware release
over the serial port.
If Port and Net A are also
flashing Red/Green, then the
module is performing a
self-test.
No action required.