EtherNet/IP Objects C-7
Instance Attributes
Important: Setting a Register object instance attribute can be done only
when the Control Timeout (class attribute 100) has been set
to a non-zero value.
Register Object (Continued)
Attribute
ID Access Rule Name Data Type Description
1 Get Bad Flag BOOL If set to 1, then attribute 4 may contain invalid,
bad or otherwise corrupt data.
0 = good
1 = bad
2 Get Direction BOOL Direction of data transfer
0 = Producer Register (drive to EtherNet/IP)
1 = Consumer Register (EtherNet/IP to drive)
3 Get Size UINT Size of register data in bits
4 Conditional
(1)
Data ARRAY of
BITS
Data to be transferred
(1)
The access rule of Set is optional if attribute 2, Direction = 1. If Direction = 0, the access rule is
Get.
Service Code
Implemented for:
Service NameClass Instance
0x0E Yes Yes Get_Attribute_Single
0x10 Yes Yes Set_Attribute_Single