Medium VoltageSMC Flex™Motor ControllerBulletins 1503E, 1560Eand 1562EUser Manual
1560E-UM050B-EN-P - June 2013Preface
6-2 Optio1560E-UM050B-EN-P - June 2013Human Interface Module(cont.)Option Action Operation Pump Control II The green start button, when presse
Options 6-3 1560E-UM050B-EN-P - June 2013Programming Parameters The following table provides the option-specific parameters that areprovided with ea
6-4 Options1560E-UM050B-EN-P - June 2013Option Parameter Range Braking Control Ë SMC Option This parameter identifies the type of control pre
Options 6-5 1560E-UM050B-EN-P - June 2013Control Wiring Refer to Chapter 1 – Product Overview for typical control wiring examplesused with various c
6-6 Options1560E-UM050B-EN-P - June 2013
Chapter 7DiagnosticsOverview This chapter describes the fault diagnostics of the MV SMC-Flexcontroller. Further, this section describes the condition
7-2 Diagnostics1560E-UM050B-EN-P - June 2013Clear Fault You can clear a fault using any of several methods:• Program the SMC-Flex controller for a Cle
Diagnostics 7-3 1560E-UM050B-EN-P - June 2013Fault CodesTable 7.A provides a complete cross-reference of the available fault codesand corresponding
7-4 Diagnostics1560E-UM050B-EN-P - June 2013Fault Definitions Table 7.B shows the fault definition for the SMC-Flex.Table 7.B – Fault Definitions Ì F
CommunicationsOverview The SMC-Flex provides advanced communications capabilities that allowit to be started and stopped from multiple sources as well
Product OverviewManual Objectives This manual is intended for use by personnel familiar with Medium Voltage andsolid-state power equipment. The manua
8-2 Communications1560E-UM050B-EN-P - June 2013Human Interface Module (cont.) Keypad DescriptionThe functions of each programming key are described be
Communications 8-3 1560E-UM050B-EN-P - June 2013The control panel provides the operator inteface to the controller.II Start The green start button,
8-4 Communications1560E-UM050B-EN-P - June 2013Connecting the Human Interface Module to the ControllerFigure 8.1 shows the connection of the SMC-Flex
Communications 8-5 1560E-UM050B-EN-P - June 2013Series A1. Disconnect the HIM and allow to power down.2. Reconnect the HIM. On Initializing screen,
8-6 Communications1560E-UM050B-EN-P - June 2013If enabling control from the built-in SMC-Flex programmer, the LogicMask must be set as follows:Table 8
Communications 8-7 1560E-UM050B-EN-P - June 2013The default configuration for I/O is 4 bytes in and 4 bytes out (TX =4 bytes, RX = 4 bytes) and is a
8-8 Communications1560E-UM050B-EN-P - June 2013SMC-Flex Bit IdentificationTable 8.G – Logic Status Word Bit # 15 14 13 12 11 10 9 8 7 6 5 4
Communications 8-9 1560E-UM050B-EN-P - June 2013Reference/Feedback The SMC-Flex does not offer the analog Reference feature. The analogFeedback feat
8-10 Communications1560E-UM050B-EN-P - June 2013Configuring DataLinks DataLinks are supported in the SMC-Flex. A DataLink is a mechanismused by most d
Chapter 9TroubleshootingGeneral Notes and Warnings For safety of maintenance personnel as well as others who might be exposedto electrical hazards ass
1-2 Product Overview%5-"%.0*UNE%5-"%.0*UNE%5-"%.0*UNEDescription (cont.) 1
9-2 Troubleshooting%5-"%.0*UNEImportant: In the case of the 1503E, refer to applicable documentationfrom OEM for troubleshooti
Troubleshooting 9-3%5-"%.0*UNETable 9.A – Fault Display ExplanationDisplay FaultCode Possible Causes Possible SolutionsLine
9-4 Troubleshooting%5-"%.0*UNETable 9.A – Fault Display Explanation (cont.)Display FaultCode Possible Causes Possible Solutions
Troubleshooting 9-5%5-"%.0*UNETable 9.D – Motor Stops While RunningDisplay Possible Causes Possible SolutionsFault displayed
9-6 Troubleshooting%5-"%.0*UNEControl Module Removal The control module is not intended for field repair. The entire modulemus
Troubleshooting 9-7%5-"%.0*UNEThe most straightforward means of checking the feedback circuits is toperform the "snubbe
9-8 Troubleshooting%5-"%.0*UNE1. Ensure there is no power to the equipment.To prevent electrical shock, ensure the main power h
Troubleshooting 9-9%5-"%.0*UNEIGDPS Boards MV SMC units provided with optional stop capabilities (soft stop, lineardecelerat
9-10 Troubleshooting%5-"%.0*UNEIGDPS Board LEDs A green LED is provided inside each of the six (6) output module boxes(channels
Troubleshooting 9-11%5-"%.0*UNECircuit Board Replacement The replacement of printed circuit boards is straightforward, howev
Product Overview 1-3%5-"%.0*UNE%5-"%.0*UNESMC-Flex™ Control Module (cont.)Other features that off
9-12 Troubleshooting%5-"%.0*UNEPower Circuit Thyristor (SCR) TestingTroubleshootingIf a power semiconductor is suspected of mal
Troubleshooting 9-13%5-"%.0*UNE5. Complete heatsink assemblies with matched SCRs are available as arenewal part (see Appendi
9-14 Troubleshooting%5-"%.0*UNESCR Replacement Procedure (cont.)6. Remove two (2) nuts at bottom front of heatsink assembly so
Troubleshooting 9-15%5-"%.0*UNESCR Replacement Procedure (cont.)Important: DO NOT loosen any of the nuts on the fiber rods
9-16 Troubleshooting%5-"%.0*UNEPower Circuit SCR Replacement Procedure (cont.)Troubleshooting (cont.)C. Install Refurbished St
Troubleshooting 9-17%5-"%.0*UNEFigure 9.4 – Upper Low Voltage Panel and Power Cell Detail (1562E) • 2400 to 4160 V, 180/360
9-18 Troubleshooting%5-"%.0*UNEHeatsink3Heatsink 2Heatsink 1SCR 2SCR 1Heatsink3Heatsink 2Heatsink 1SCR 2SCR 1Figure 9.5 – Power
Troubleshooting 9-19%5-"%.0*UNETo Remove SCR:• Remove shorting bar hardware• Pry opposing Heatsinks apart• ExtractSCRTo Inse
9-20 Troubleshooting%5-"%.0*UNEHeatsink 1SCR1SCR 2SCR3SCR4Heatsink2Heatsink 3Heatsink 4Heatsink 5Note: SCR 1 and SCR 3 are a ma
Troubleshooting 9-21%5-"%.0*UNETo Remove SCR4:• Remove shorting bar hardware• Pry Heatsinks 4 and 5 apart• ExtractSCRTo Inse
1-4 Product Overview%5-"%.0*UNEStarting Modes (cont.) Selectable Kickstart :Selectable kickstart provides a power boost at sta
9-22 Troubleshooting%5-"%.0*UNEGate Driver BoardsLine ConnectionLoad ConnectionGate Driver BoardsLine ConnectionLoad Connection
Troubleshooting 9-23%5-"%.0*UNEModule retaining hardware locations (4)Line ConnectionLoad ConnectionModule retaining hardwar
9-24 Troubleshooting%5-"%.0*UNEDo not loosenCentre NutLocking Nut(Do not adjust)Indicating WasherDo not loosenGapTo remove clam
Troubleshooting 9-25%5-"%.0*UNEHeatsink AssemblySnubber CapacitorFrame AssemblyGate Driver BoardSharingResistorSnubberResist
9-26 Troubleshooting%5-"%.0*UNEHeatsink AssemblySnubber CapacitorGate Driver BoardsFrame AssemblySnubber ResistorsSharing Resis
Troubleshooting 9-27%5-"%.0*UNEIf the resistance checks from the Thyristor testing section were abnormaland the thyristors c
9-28 Troubleshooting%5-"%.0*UNETo Interface boardGround ConnectionsMeasure11.3 kΩTap D2MΩTap C4.3 MΩTap B9.5 MΩTap A15 MΩVOLTAG
Troubleshooting 9-29%5-"%.0*UNEMeasure across R36, R73, R110, R147, R184 and R221 located at thebottom of each leg of the mo
9-30 Troubleshooting%5-"%.0*UNESnubber Resistor Replacement When replacing the ceramic wire-wound type snubber resistors, useca
Troubleshooting 9-31%5-"%.0*UNEFigure 9.21A – 1500/2400 V Module Wiring (180/360 A) (Without Option
Product Overview 1-5%5-"%.0*UNEDual Ramp Start :This starting mode is useful for applications that have varying loads (andth
9-32 Troubleshooting%5-"%.0*UNEFigure 9.21B – 1500/2400 V Module Wiring (600 A) (Without Optional Pump
Troubleshooting 9-33%5-"%.0*UNEFigure 9.22A – 1500/2400 V Module Wiring (180/360 A) (With Optional
9-34 Troubleshooting%5-"%.0*UNEFigure 9.22B – 1500/2400 V Module Wiring (600 A) (With Optional Pump Co
Troubleshooting 9-35%5-"%.0*UNEFigure 9.23A – 3300/4160 V Module Wiring (180/360 A) (Without Option
9-36 Troubleshooting%5-"%.0*UNEFigure 9.23B – 3300/4160 V Module Wiring (600 A) (Without Optional Pump
Troubleshooting 9-37%5-"%.0*UNEFigure 9.24A – 3300/4160 V Module Wiring (180/360 A) (With Optional
9-38 Troubleshooting%5-"%.0*UNEFigure 9.24B – 3300/4160 V Module Wiring (600 A) (With Optional Pump Co
Troubleshooting 9-39%5-"%.0*UNEFigure 9.25 – 6900 V Module Wiring (180/360/600 A) (Without Optional P
9-40 Troubleshooting%5-"%.0*UNEFigure 9.26 – 6900 V Module Wiring (180/360/600 A) (With Optional Pump Co
Chapter 10MaintenanceSafety and Preventative The Maintenance Technician should become familiar with the layout andbe aware of the basic system paramet
1-6 Product Overview%5-"%.0*UNEStarting Modes (cont.) Preset Slow SpeedThis option can be used in applications that require a s
10-2 Maintenance1560E-UM050B-EN-P - June 2013Periodic Inspection (cont.) Allen-Bradley magnetic starters, contactors and relaysare designed to operate
Maintenance 10-3 1560E-UM050B-EN-P - June 2013Solid-State DevicesSolid-state devices require little more than a periodic visual inspection.Printed c
10-4 Maintenance1560E-UM050B-EN-P - June 2013Periodic Inspection (cont.) "Keep Good Maintenance Records"This rule will be most helpful in lo
Maintenance 10-5 1560E-UM050B-EN-P - June 2013Hazardous materialsEnvironmental protection is a top priority for Rockwell Automation.The facility tha
10-6 Maintenance1560E-UM050B-EN-P - June 2013• Chromate PlatingSome sheet steel and fasteners are plated with zinc and sealed with achromate-based dip
Appendix A1560E/1562E SMC-Flex Specifications 1560E-UM050B-EN-P - June 2013Table A.1 – Specifications Electrical Ratings UL/CSA/NEMA IEC Power
A-2 Specifications1560E-UM050B-EN-P - June 2013Table A.1 – Specifications (cont.) Electrical Ratings (cont.) UL/CSA/NEMA IEC Short Circuit Prote
Specifications A-3 1560E-UM050B-EN-P - June 2013 Table A.1 – Specifications (cont.) Environmental Ratings UL/CSA/NEMA IEC Operating Temperature
A-4 Specifications1560E-UM050B-EN-P - June 2013Table A.4 – Cable Quantity and Size Bulletin Size Structure Code Unit Size Inches (mm) Max. No. &
Specifications A-5 1560E-UM050B-EN-P - June 2013Table A.5 – Shipping Weights and Dimensions u Horsepower (kW) Dimensions in inches (mm) Shipping W
Product Overview 1-7%5-"%.0*UNELinear Speed Acceleration and DecelerationThe SMC-Flex has the ability to control the motor s
A-6 Specifications11560E-UM050B-EN-P - June 2013Table A.6 – Power Bus and Ground Bus Description Specifications Main Horizontal Power Bus Bus Bar Mat
Specifications A-7 1560E-UM050B-EN-P - June 2013Table A.7 – Power Fuses and Losses Description Specifications Power Fuses and Fuse Holders This se
A-8 Specifications1560E-UM050B-EN-P - June 2013Table A.8 – Control Wire and Power Wire Description Specifications Control Wire All Medium Voltage stru
Appendix BParameter Information 1560E-UM050B-EN-P - June 2013 Table B.1 – Parameter List Group Parameter Description Parameter Number Units Min /
B-2 Parameter Information1560E-UM050B-EN-P - June 2013Table B.1 – Parameter List (cont.) Group Parameter Description Parameter Number Units Min / M
Parameter Information B-3 1560E-UM050B-EN-P - June 2013Table B.1 – Parameter List (cont.) Group Parameter Description Parameter Number Units Min
B-4 Parameter Information1560E-UM050B-EN-P - June 2013Table B.1 – Parameter List (cont.) Group Parameter Description Parameter Number Units Min / M
Appendix C1560E and 1562E Relay ControlFunctional Description The following functional descriptions and associated control circuits arefor units usin
C-2 1560E and 1560E Relay Control1560E-UM050B-EN-P - June 2013Functional Description (cont.) Bulletin 1562E • Basic Control – With Controlled StopWhen
1560E and 1560E Relay Control C-3 1560E-UM050B-EN-P - June 2013Bulletin 1560E • Basic Control – Controlled Start OnlyThe Bulletin 1560E is intended
1-8 Product Overview%5-"%.0*UNE%5-"%.0*UNE%5-"%.0*UNEStarting Modes (cont.)
C-4 1560E and 1560E Relay Control1560E-UM050B-EN-P - June 2013Figure C.1 – Bulletin 1562E Relay Control Circuit • Without Stop Control
1560E and 1560E Relay Control C-5 1560E-UM050B-EN-P - June 2013Figure C.2 – Bulletin 1562E Relay Control Circuit • With Stop Control
C-6 1560E and 1560E Relay Control1560E-UM050B-EN-P - June 2013Figure C.3 – Bulletin 1562E Relay Control Circuit • With DeviceNet (or DPI) Communicatio
1560E and 1560E Relay Control C-7 1560E-UM050B-EN-P - June 2013Figure C.4 – Bulletin 1560E Relay Control Circuit • Without Stop Control
C-8 1560E and 1560E Relay Control1560E-UM050B-EN-P - June 2013Figure C.5 – Bulletin 1560E Relay Control Circuit • With Stop Control
1560E and 1560E Relay Control C-9 1560E-UM050B-EN-P - June 2013Figure C.6 – Bulletin 1560E Relay Control Circuit • With DeviceNet (or DPI) Communica
C-10 1560E and 1560E Relay Control111560E-UM050B-EN-P - June 2013
Appendix DSpare Parts 1560E-UM050B-EN-P - June 2013Table D.1 Bulletin 1503E • 1000-1500 Volt, 180/360 Amp, 6-device Ì Qty per controller Descripti
D-2 Spare Parts1560E-UM050B-EN-P - June 2013Table D.2 Bulletin 1503E, 1560E, 1562E • 2300 Volt, 180/360 Amp, 6-device Í Qty per controller Descripti
Spare Parts D-3 1560E-UM050B-EN-P - June 2013Table D.3 Bulletin 1503E, 1560E, 1562E • 2300 Volt, 600 Amp, 6-Device Ë Qty per controller Descriptio
Product Overview 1-9%5-"%.0*UNEProtection and Diagnostics The MV SMC-Flex™ controller is capable of providing the followingp
D-4 Spare Parts1560E-UM050B-EN-P - June 2013Table D.4 Bulletin 1503E, 1560E, 1562E • 3300 and 4160 Volt, 180/360 Amp, 12-device Í Qty per controller
Spare Parts D-5 1560E-UM050B-EN-P - June 2013Table D.5 Bulletin 1503E, 1560E, 1562E • 3300 and 4160 Volt, 600 Amp, 12-device Ë Qty per controller D
D-6 Spare Parts1560E-UM050B-EN-P - June 2013Table D.6 Bulletin 1503E, 1560E, 1562E • 5500/6900 Volt, 180/360 Amp, 18-device Í Qty per controller Desc
Spare Parts D-7 1560E-UM050B-EN-P - June 2013Table D.7 Bulletin 1503E, 1560E, 1562E • 5500/6900 Volt, 600 Amp, 18-device Ë Qty per controller Descr
D-8 Spare Parts1560E-UM050B-EN-P - June 2013Table D.8 Accessories Qty per controller Description Part Number Control Module (Standard) 41391-454-
Appendix EAccessories 1560E-UM050B-EN-P - June 2013Table E.1 Accessories Description Description/Used With Catalog Number HIM Remote Door Mounted
E-2 Accessories1560E-UM050B-EN-P - June 2013
Medium Voltage Business, 135 Dundas Street, Cambridge, ON N1R 5X1 Canada, Tel: (1) 519 623-1810, Fax: (1) 519 623-8930 Web Site: www.ab.com/
Important User InformationRead this document and the documents listed in the Additional Resources section about installation, configuration, and opera
1-10 Product Overview%5-"%.0*UNEApproximate trip time for 3-phase balancedcondition from cold start.Approximate trip time for 3
Product Overview 1-11%5-"%.0*UNEUnderload :Utilizing the underload protection of the MV SMC-Flex controller, motoroperation
1-12 Product Overview%5-"%.0*UNEUnbalance :The MV SMC-Flex is able to detect an unbalance in line voltages. Motoroperation can
Product Overview 1-1%5-"%.0*UNE600%PercentFull LoadCurrentJamTime (seconds)RunningUser ProgrammedTrip Level600%PercentFull L
1-14 Product Overview%5-"%.0*UNEGround Fault Trip (cont.)Parameter 74, Gnd Flt Delay, allows the installer to define the time
Product Overview 1-15%5-"%.0*UNETable 1.A –PTC Input RatingsResponse Resistance 3400 Ω ± 150 ΩReset Resistance 1600 Ω ± 100
1-16 Product Overview%5-"%.0*UNEOpen GateAn open-gate fault indicates that improper SCR firing, typically caused byan open SCR
Product Overview 1-17%5-"%.0*UNEExcessive Starts/HourThe MV SMC-Flex™ module allows the user to program the desirednumber of
1-18 Product Overview%5-"%.0*UNECommunication A serial interface port (DPI) is provided as standard, which allowsconnection to
Product Overview 1-19%5-"%.0*UNEStatus Indication Four programmable hard contact outputs are provided as standard:• The Aux
1560E-UM050B-EN-P - June 2013PagePreface Service Procedure... P-1Product O
1-20 Product Overview%5-"%.0*UNEControl Options (cont.) Pump Application Considerations1. Consult factory if start time setting
Product Overview 1-21%5-"%.0*UNEPump stopping is not intended to be used as anemergency stop. Refer to the applicable stand
1-22 Product Overview%5-"%.0*UNEHardware Description The following sections contain descriptions of system components andsystem
Product Overview 1-23%5-"%.0*UNEInterface BoardThis circuit board takes current transformer signals plus line-side and load-
1-24 Product Overview%5-"%.0*UNEFigure 1.18 – Typical MV SMC-Flex Power System • Bulletin 1562E (Without Stop Control)*
Product Overview 1-25%5-"%.0*UNEFigure 1.19 – Typical MV SMC-Flex Power System • Bulletin 1562E (With Stop Control)
1-26 Product Overview%5-"%.0*UNEFigure 1.20 – Typical MV SMC-Flex Power System • Bulletin 1560E (Without Stop Control)
Product Overview 1-27%5-"%.0*UNEFigure 1.21– Typical MV SMC-Flex Power System • Bulletin 1560E (With Stop Control)
1-28 Product Overview%5-"%.0*UNEFunctional Description The following functional descriptions and associated control circuits ar
Product Overview 1-29%5-"%.0*UNEBulletin 1562E • Basic Control – With Controlled StopWhen wired as shown in Figure 1.23, the
1560E-UM050B-EN-P - June 2013ii Table of Contents – MV Dialog Plus Medium Voltage Controller User ManualProduct Overview (cont.) Chapter 1 PageTypical
1-30 Product Overview%5-"%.0*UNEFunctional Description (cont.) Bulletin 1560E • Basic Control – Controlled Start OnlyThe Bullet
Product Overview 1-31%5-"%.0*UNEBulletin 1560E • DPI Control – Controlled Start onlyThe control scheme shown in Figure 1.27
1-32 Product Overview%5-"%.0*UNEFigure 1.22 – Bulletin 1562E IntelliVAC Control Circuit • Without Stop Control
Product Overview 1-33%5-"%.0*UNEFigure 1.23 – Bulletin 1562E IntelliVAC Control Circuit • With Stop Control
1-34 Product Overview%5-"%.0*UNE%5-"%.0*UNEFigure 1.24 – Bulletin 1562E IntelliVAC Control Circuit
Product Overview 1-35%5-"%.0*UNEFigure 1.25 – Bulletin 1560E IntelliVAC Control Circuit • Without Stop Control
1-36 Product Overview%5-"%.0*UNEFigure 1.26 – Bulletin 1560E IntelliVAC Control Circuit • With Stop Control
Product Overview 1-37%5-"%.0*UNEFigure 1.27 – Bulletin 1560E IntelliVAC Control Circuit
1-38 Product Overview%5-"%.0*UNE
InstallationPerform the installation duties correctly. Errors maycause commissioning delays, equipment damage orpersonal injury.Important: For the 1
1560E-UM050B-EN-P - June 2013Table of Contents – MV Dialog Plus Medium Voltage Controller User Manual iiiInstallation (cont.) Chapter 2 PageSurge A
2-2 Installation%5-"%.0*UNEGeneral Precautions In addition to the precautions listed throughout this manual, the followingstat
Installation 2-3%5-"%.0*UNEInstallation Site Consider the following when selecting the installation site:A. The operating am
2-4 Installation%5-"%.0*UNEInstallation Site (cont.) Grounding PracticesThe purpose of grounding is to:A. Provide safety for Pe
Installation 2-5%5-"%.0*UNEPower Connections The controller requires a three-phase supply and an equipment groundingconductor
2-6 Installation%5-"%.0*UNEPower Connections (cont.)PowerStackAssemblyBypass Vacuum ContactorVoltage Sensing ModuleNon Load Bre
Installation 2-7%5-"%.0*UNEPower Cable LugsGround Bus LugPower Cable LugsGround Bus LugFigure 2.2 – Incoming Line Cable Conn
2-8 Installation%5-"%.0*UNEPower Connections (cont.) Bulletin 1560ERefer to Figures 2.4 to 2.6 to make power connections for a
Installation 2-9%5-"%.0*UNEPhase 1Line ConnectionPhase 2Line ConnectionLoad Connections(top exit shown)Phase 1 (front)throug
2-10 Installation%5-"%.0*UNEPower Connections (cont.)Phase 1Line ConnectionPhase 2Line ConnectionLoad Connections(top exit show
Installation 2-11%5-"%.0*UNEImportant: For retrofit units (Bul. 1560E), the CEC and NEC require thatbranch-circuit protecti
1560E-UM050B-EN-P - June 2013iv Table of Contents – MV Dialog Plus Medium Voltage Controller User ManualMetering Chapter 5 PageOverview...
2-12 Installation%5-"%.0*UNEPower Wiring The wire sizes must be selected individually, observing all applicablesafety and CEC o
Installation 2-13%5-"%.0*UNEInstallation Physical LocationThe controller is designed for limited front access (components ma
2-14 Installation%5-"%.0*UNEInstallation (cont.) Power Factor Correction CapacitorsThe controller can be installed on a system
Installation 2-15%5-"%.0*UNEPower BusIsolation Switch Isolation SwitchFuseFuseContactorIsolation ContactorPFCCdi/dt Inductor
2-16 Installation%5-"%.0*UNERockwell Automation highly recommends that motor surge capacitors and/ormotor surge arresters not
Installation 2-17%5-"%.0*UNEMotor Overload Protection Thermal motor overload protection is provided as standard (though it m
2-18 Installation%5-"%.0*UNEThis product has been designed for Class A equipment.Use of the product in domestic environments m
Installation 2-19%5-"%.0*UNE• To meet produce susceptibility requirements, ferrite cores need to beadded to the communicatio
2-20 Installation%5-"%.0*UNEControl Terminal Designations As shown in Figure 2.10, the SMC-Flex controller contains 24 controlt
Commissioning ProcedurePreliminary Set-Up A. Ensure the work area is clean and tidy. Pathways to main disconnectand emergency stop push-button must b
1560E-UM050A-EN-P – August 2004Table of Contents – MV Dialog Plus Medium Voltage Controller User Manual vTroubleshooting Chapter 9 PageGeneral Notes a
3-2 Commissioning Procedures11560E-UM050B-EN-P - June 2013System CharacteristicsJob Name: _____________________________ Job Number: __________________
Commissioning Procedures 3-3 1560E-UM050B-EN-P - June 2013Preliminary Check Ensure that all sources of power are isolated and lockedout before worki
3-4 Commissioning Procedures1560E-UM050B-EN-P - June 2013Hi-Pot and Megger Test It is recommended that insulation levels be checked before energizing
Commissioning Procedures 3-5 1560E-UM050B-EN-P - June 2013***Points for disconnection, to allow Hi-Potor Megger tests (refer to Chapter 3) ** *****
3-6 Commissioning Procedures1560E-UM050B-EN-P - June 2013SW2: When ON (up) provides test pulses to gate driver circuits.NOTE: Must be OFF (down) for
Commissioning Procedures 3-7 1560E-UM050B-EN-P - June 2013Power Supply Tests Servicing energized industrial control equipment can behazardous. Seve
3-8 Commissioning Procedures1560E-UM050B-EN-P - June 2013Power Supply Tests (cont.) NOTE: Systems with optional Pump Control or Soft Stop includecont
Commissioning Procedures 3-9 1560E-UM050B-EN-P - June 20137. The gate-driver board voltage may be checked by connecting a DCvoltmeter to TP2 (+) an
3-10 Commissioning Procedures1560E-UM050B-EN-P - June 201310. When each gate driver circuit has been checked, disconnect the powersupply and remove it
Commissioning Procedures 3-11 1560E-UM050B-EN-P - June 2013Resistance Checks To ensure that resistors and connections have not been damaged duringsh
1560E-UM050A-EN-P – August 2004vi Table of Contents – MV Dialog Plus Medium Voltage Controller User ManualAppendix A 1560E/1562E SMC-Flex Specificatio
3-12 Commissioning Procedures1560E-UM050B-EN-P - June 2013Table 3.B – Input Voltage Ranges Tap Voltage Range MV Ratio D 800 – 1449 V 1020 C 1450
ProgrammingOverview This chapter provides a basic understanding of the programming keypadbuilt into the SMC-Flex controller. This chapter also descri
4-2 Programming1560E-UM050B-EN-P - June 2013Programming Menu (cont.)DevicePower-up andStatus DisplayParameterMemoryStoragePreferencesDiagnosticsSelect
Programming 4-3 1560E-UM050B-EN-P - June 2013ParameterMotorSet Up UtilityLinear ListProtectionParameterMonitoringCommunicationsuwvEscParameterMotorS
4-4 Programming1560E-UM050B-EN-P - June 2013Programming Menu (cont.) Table 4.AParameter Linear ListParameter No. Description Parameter No. Descript
Programming 4-5 1560E-UM050B-EN-P - June 2013Password The SMC-Flex Controller allows the user to limit access to theprogramming system through passw
4-6 Programmi1560E-UM050B-EN-P - June 2013Parameter Management Before you begin programming, it is important to understand how thecontroller memory is
Programming 4-7 1560E-UM050B-EN-P - June 2013Using Parameter ManagementDescription Action Display Saving to EEPROM To ensure that the newly modi
4-8 Programming1560E-UM050B-EN-P - June 2013Parameter Modification All parameters are modified using the same method. The basic steps toperforming pa
Programming 4-9 1560E-UM050B-EN-P - June 2013Soft Start The following parameters are specifically used to adjust the voltage rampsupplied to the mot
1560E-UM050B-EN-P - June 2013Service Procedure For your convenience, the Rockwell Automation Global ManufacturingSolutions (GMS), provides a
4-10 Programming1560E-UM050B-EN-P - June 2013Dual Ramp Start The SMC-Flex controller provides the user with the ability to selectbetween two Start set
Programming 4-11 1560E-UM050B-EN-P - June 2013Full Voltage Start The SMC-Flex controller may be programmed to provide a full voltagestart (output vo
4-12 Programming1560E-UM050B-EN-P - June 2013Parameter Option Current Limit Level v The current limit level that is applied for the Ramp time selecte
Programming 4-13 1560E-UM050B-EN-P - June 2013Motor Protection While the Basic Set Up group allows the user to get started with aminimum number of p
4-14 Programming1560E-UM050B-EN-P - June 2013Example Settings Undervoltage uWith Line Voltage programmed for 4160 V and the Undervoltage levelprogramm
Programming 4-15 1560E-UM050B-EN-P - June 2013Motor Information The Basic Set Up and Overload programming group allows the user to setparameters ind
4-16 Programming1560E-UM050B-EN-P - June 2013
MeteringOverview While the SMC-Flex controller operates your motor, it also monitorsseveral different parameters, providing a full function metering
5-2 Metering1560E-UM050B-EN-P - June 2013Viewing Metering Data(cont.)Description Action Display 7. Scroll through the Metering parameters with
OptionsOverview The SMC-Flex controller offers a variety of unique control programmingand communication options that provide enhanced capabilities. (
Comentarios a estos manuales