8-8 Communications
1560E-UM050B-EN-P - June 2013
SMC-Flex Bit Identification
Table 8.G Logic Status Word
Bit #
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status Description
X Enabled
1 Control Power Applied
0 No Control Power
X Running
1 Power Applied to Motor
0 Power not Applied to Motor
X Phasing
1 ABC Phasing
0 CBA Phasing
X
Phasing
Active
1 3-phase is valid
0 No valid 3-phase is detected
X
Starting
(Accel)
1 Performing a Start Maneuver
0 Not performing a Start Maneuver
X
Stopping
(Decel)
1 Performing a Stop Maneuver
0 Not performing a Stop Maneuver
X Alarm
1 Alarm Present
0 No Alarm Present
X Fault
1 Fault Condition Exists
0 No Fault Condition
X At Speed
1 Full Voltage Applied
0 Not Full Voltage Applied
X
Start/
Isolation
1 Start/Isolation Contactor Enabled
0 Start/Isolation Contactor Disabled
X Bypass
1 Bypass Contactor Enabled
0 Bypass Contactor Disabled
X Ready
1 Ready
0 Not Ready
Bits 12 to 15 Not Used
Table 8.H Logic Command Word
Bit #
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status Description
X Stop
1 Stop/Inhibit
0 No Action
X Start
1 Start
0 No Action
X
Option #1
Input
1 Stop Maneuver/Inhibit
0 No Action
X
Clear
Faults
1 Clear Faults
0 No Action
X
Option #2
Input
1 Perform Option 2 function
0 No Action
Bits 5 to 15 Not Used