Rockwell-automation 1560E SMC Flex Smart Motor Controller Manual de usuario Pagina 177

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 198
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 176
Appendix C
1560E and 1562E Relay Control
Functional Description The following functional descriptions and associated control circuits are
for units using electromechanical (relay) control.
Bulletin 1562E • Basic Control – Controlled Start only
When wired as shown in Figure C.1, the controller operates as follows:
Pressing the "Start" button initiates the start sequence. Relay "CR" closes
and applies control power to terminal 17 of the SMC-Flex module. The
auxiliary contact #2 (set for "normal") closes, picking up "MC", which
completes the hold-in circuit on the start button, and closes the main
contactor.
The SMC-Flex module examines the line voltage, looks for fault
conditions, checks phase rotation, calculates zero crossing information,
and begins gating the SCRs to start the motor.
When the motor approaches rated speed, the SMC-Flex module closes the
"AUX1" (up-to-speed) auxiliary contacts, closing relay "BC", which closes
the bypass contactor. The motor then runs at full line voltage.
When the "Stop" button is pressed, the "CR" relay opens terminal 17 on
the SMC-Flex module. The "AUX2" (Normal) contact opens, dropping
out the main contactor, allowing the motor to stop. The "AUX1" contact
also opens, but "BC" is held closed for a short time by the control module.
This holds the bypass contactor closed for about 10 seconds to protect the
power electronics from any voltage transients due to opening the motor
circuits.
1560E-UM050B-EN-P - June 2013
Vista de pagina 176
1 2 ... 172 173 174 175 176 177 178 179 180 181 182 ... 197 198

Comentarios a estos manuales

Sin comentarios