9-4 Troubleshooting
%5-"%.0*UNE
Table 9.A Fault Display Explanation (cont.)
Display FaultCode Possible Causes Possible Solutions
Phase Reversal 26 Incoming supply voltage is not in
the expected ABC sequence
Check power wiring
Disable protection if not needed
Comm Loss 27, 28, 29 Communication disconnection at
the serial port
Check for a communication cable disconnection to the
SMC-Flex controller
Network 30, 31, 32 DPI network loss Reconnect for each DPI connected device
Ground Fault 33 Ground fault current level has
exceeded programmed values
Check power system and motor; correct if necessary
Check programmed ground fault levels to match
application requirements
Excess Starts/Hr. 34 Number of starts in a one-hour
period has exceeded the value
programmed
Wait an appropriate amount of time to restart
Consult factory if more than 2 starts per hour are
required
Power Loss :
(with phase indication)
35, 36, 37 Missing supply phase (as indicated)
Loss of feedback
Check for open line (i.e., blown line fuse)
Check CT connections, replace Interface board
Hall ID 38 Faulty interface Check ribbon cable connections between interface
board and control module
Replace interface board
NVS Error 39 Data entry error Check user data and perform a User Store function
Replace control module
System Faults 128 to 209 Control module internal fault Cycle control power to reset the control module
If fault persists, replace control module
: Prestart fault indication
Table 9.B – Motor Will Not Start No Output Voltage to the Motor
Display Possible Causes PossibleSolutions
Fault displayed See fault description See Table 9.A addressing fault conditions
Display is blank Control voltage is absent
Failed control module
Check control wiring and correct if necessary
Replace control module
Stopped
0.0 Amps
Pilot devices
SMC Enable input is open at
terminal 13
Terminal 16 is open
Start-Stop control has not been
enabled for the human interface
module
Control voltage
Failed control module
Check wiring
Check wiring
Check wiring
Follow the instructions on page 2-16 to 2-18
to enable control capability
Check control voltage
Replace control module
Starting Two or three power phases are
missing
Check power system
Check voltage sensing module and connections
Table 9.C – MotorRotates (but does not accelerate to full speed)
Display Possible Causes PossibleSolutions
Fault displayed See fault description See Table 9.A addressing fault conditions
Starting Mechanical problems
Inadequate Current Limit setting
Failed control module
Check for binding or external loading and correct
Check motor
Adjust the Current Limit Level to a higher setting
Replace control module