Rockwell-automation 1560E SMC Flex Smart Motor Controller Manual de usuario Pagina 91

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 198
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 90
Programming 4-11
1560E-UM050B-EN-P - June 2013
Full Voltage Start The SMC-Flex controller may be programmed to provide a full voltage
start (output voltage to the motor reaches full voltage within 1/4 second)
with the following programming:
Parameter Option
Starting Mode
This must be programmed for Full Voltage.
Full Voltage
Linear Speed The SMC-Flex provides the user the ability to control the motor speed
during starting and stopping maneuvers. A tach input is required as
specified in Linear Speed Acceleration on page 1-7.
Parameter Option
Starting Mode
This must be programmed for Linear Speed.
Linear Speed
Ramp Time
This programs the time period that the controller
will ramp from 0 speed to full voltage.
0 to 30 s
Kickstart Time
A boost of current is provided to the motor for the
programmed time period.
0.0 to 2.2 s
Kickstart Level
Adjusts the amount of current applied to the motor
during the kickstart time.
0 to 90/% locked rotor torque
Basic Setup The Basic Setup programming group provides a limited parameter set,
allowing quick start-up with minimal adjustments. If the user is planning
to implement some of the advanced features (i.e., Dual Ramp, Unbalance
Level, etc.), then the Linear List programming group should be selected.
It provides all the Basic Setup parameter set plus the advanced set.
Parameter Option
SMC Option
Displays the type of controller. This is factory set
and not adjustable.
Standard
Motor Connection
Displays the motor type the device is being
connected to.
Line or Delta
Line Voltage
Displays the system line voltage the unit is
connected to.
MV Ratio
Scales the output from the Voltage Sensing Board
to display correct line voltage.
1 to 10000
(See Table 3.B Input
Voltage Ranges)
Starting Mode
Allows the user to program the SMC-Flex controller
for the type of starting that best fits the application.
Soft Start, Current Limit,
Full Voltage, Linear Speed
Ramp Time
This sets the time period during which the controller
will ramp the output voltage.
0 to 30 s
Initial Torque u
The initial reduced voltage output level for the voltage
ramp is established and adjusted with this parameter.
0 to 90/% locked rotor torque
u Starting Mode must be programmed to Soft Start to obtain access to the Initial Torque parameter.
Vista de pagina 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 197 198

Comentarios a estos manuales

Sin comentarios