A-2 Specifications
1560E-UM050B-EN-P - June 2013
Table A.1 – Specifications (cont.)
Electrical Ratings (cont.) UL/CSA/NEMA IEC
Short Circuit Protection
The power electronics unit must be protected by current -limiting fuses (to be included by customer in existing starter with
1560E). The combination controller includes appropriate fusing (coordinated with motor).
Fault Level Withstand as a Fused (E2)
Controller NEMA E2
2400 V 200 MVA Sym
4160 V 350 MVA Sym
4600 V 400 MVA Sym
6900 V 570 MVA Sym
Control Circuit
Rated Operation Voltage 120/240 V AC (-15%, +10%) 110/230V ~ (-15%, +10%)
Dielectric Withstand 1600 V AC 2000 V ~
Operating Frequency 50/60 Hz 50/60 Hz
Enclosure
Enclosure Type NEMA Type 1, 1G, 12 and 3R IP 10, 21, 52 and 34
Overload Characteristics (Control Module)
Type Solid-state thermal overload with phase loss
Current Range 1.0 – 1,000 Amps
Trip Classes 10, 15, 20 and 30
Trip Current Rating 120% of Motor FLC
Number of Poles 3
Power Requirements
Control Module 75 VA
Gate Driver Boards Self-powered u
Contactor See Contactor Specifications (page 35)
Auxiliary Contacts (Control Module)
Rated Operation Voltage (Max.)
20-265 V AC
5-30 V DC (resistive)
20-265 V ~
5-30 V DC (resistive)
Rated Insulation Voltage N/A 277 V ~
Operating Frequency 50/60 Hz, DC 50/60 Hz, DC
Utilization Category
B300
30 VDC @ 0.88A pilot duty
AC-15
DC-12
Mechanical Ratings (Control Module)
Terminals
Control Terminals :
M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate
SCPD Performance Type 2
SCPD List Class CC 8A @ 1000 A Available Fault Current
DPI Communication (Control Module)
Maximum Output Current 280 mA
Metering Functionality (Control Module)
Voltage, Current, MW, MWh,
Displacement Power Factor
Yes
Tachometer Input (Control Module)
Voltage 0 – 4.5 VDC
Current 1.0 mA
u For stop maneuvers, the gate driver boards are powered using a 50 VDC supply.