Troubleshooting 9-5
%5-"%.0*UNE
Table 9.D – Motor Stops While Running
Display Possible Causes Possible Solutions
Fault displayed See fault description See Table 9.A addressing fault conditions
Display is blank Control voltage is absent
Failed control module
Check control wiring and correct if necessary
Replace control module
Stopped
0.0 Amps
Pilot devices
Failed control module
Check control wiring and correct if necessary
Replace control module
Starting Two or three power phases are
missing
Failed control module
Check power system
Check voltage sensing module and connections
Replace control module
Table 9.E – MiscellaneousSituations
Display Possible Causes Possible Solutions
Motor current and
voltage fluctuates with
steady load
Motor
Erratic Load
Verity type of motor as a standard squirrel cage induction
motor
Check load conditions
Erratic operation Loose connections Shut off all power to controller and check for loose
connections
Acceleratestoo fast Startingtime
Initial torque
Current limit setting
•Kickstart
Increase starting time
Lower initial torque setting
Decrease current limit setting
Lower kickstart time or turn off
Acceleratestoo slow Startingtime
Initial torque
Current limit setting
•Kickstart
Decrease starting time
Increase initial torque setting
Increase current limit setting
Increase kickstart time or turn off
Fan does not operate Wiring
Failed fans(s)
Check wiring and correct if necessary
Replace fan(s)
Motor stops too quickly
withSoftStopoption
Time setting Verify the programmed stopping time and correct if
necessary
Motor stops too slowly
withSoftStopoption
Stopping time setting
Misapplication
Verify the programmed stopping time and correct if
necessary
The Soft Stop option is intended to extend the stopping time
for loads that stop suddenly when power is removed from
the motor.
Fluid surges with
pumps still occur with
the Soft Stop option
Misapplication Soft Stop ramps voltage down over a set period of time. In
the case of pumps, the voltage may drop too rapidly to
prevent surges. A closed loop system such as Pump Control
would be more appropriately suited.
Refer to Publication 150-911
Motor overheats Overload
Blocked ventilation
•Dutycycle
Allow motorto cool and reduce load.
Remove blockage and ensure motor is being adequately
cooled.
Preset Slow Speed and Accu-Stop options: Extended
operation at slow speeds reduces motor cooling efficiency.
Consult motor manufacturer for motor limitations.
Smart Motor Braking option: Check duty cycle. Consult
motor manufacturer for motor limitations.
Motor short circuit Winding fault Identify fault and correct
Check forshorted SCR; replace if necessary
Ensure power terminals are secure
NOTE: For Pump Stop issues, please refer to “Pump Application Considerations” on page 1-20.