Publication 1746-UM002B-EN-P - August 2004
6-14 Application Examples
Data Table for N10 File (hexidecimal)
Data Table for N11 File (decimal)
Example 4 - Using Soft
Presets
This example illustrates the use of soft presets with the Counter
Control Block. A soft preset loads the specific counter with a preset
count value. This preset value is determined by the last min/max
Count Value Block for that counter. This block is normally loaded
during HSCE2 initialization, but the preset can be changed
dynamically (as shown in Example 5).
1. The ladder logic uses the Example 2 program (SLC 5/03 or
higher processor in Class 4, mode 1).
2. The example soft presets Counter 1 whenever the soft preset
trigger bit (B3/6) sees a positive (0 to 1) transition.
3. The soft preset must wait until after the HSCE2 initialization
process is complete (B3/0 is set).
4. The Counter Configuration Block (N10:10 to N10:17) gate/preset
mode for Counter 1 must allow soft presets. In this case, N10:11
was changed from 0C (No Preset) to 1C (Soft Preset Only).
Programming Blocks Offset 0123456789
Module Setup N10:0 1 103 80000000
Counter Configuration N10:10 F02 606000000
Min/Max Count Value Counter 1 N10:20 400019000000
Min/Max Count Value Counter 2 N10:30 104 0 0 0 1F4 00000
Min/Max Count Value Counter 3 N10:40 204 0 0 0 258 00000
Min/Max Count Value Counter 4 N10:50 304 0 0 0 2BC 00000
Counter 1 Program Ranges N10:60 10 1000311000
Counter 1 Program Ranges N10:70 10 2 0 32 0 63 2000
Counter 1 Program Ranges N10:80 10 4 0 64 0 95 4000
Counter 1 Program Ranges N10:90 10 8 0 96 0 C7 8000
Counter 1 Program Ranges N10:100 10 10 0 C8 0 F9 1000
Counter 1 Program Ranges N10:110 10 20 0 FA 0 12B 2000
Counter 1 Program Ranges N10:120 10 40 0 12C 0 15D 4000
Counter 1 Program Ranges N10:130 10 80 0 15E 0 190 8000
Counter Control N10:140 80 8001 8001 8001 8001 FF00 FF 0 0 0
Offset 0123456789
N11:0 140 140 14 0 256