Publication 1746-UM002B-EN-P - August 2004
6-18 Application Examples
Data Table for N10 File (hexidecimal)
Data Table for N11 File (decimal)
Example 5 - Change Presets
Dynamically
This example shows the user how to dynamically change the preset
value using the Min/max Count Block.
1. The following procedure uses the Example 2 program (SLC 5/03
or higher processor in Class 4, mode 1).
2. The Min/max Count Value requires the use of handshaking bits
to get the preset values into the 1746-HSCE2. Therefore, the
handshaking code is in a separate subroutine (ladder file 14).
The ladder rungs which trigger the dynamic preset change are in
the 1746-HSCE2 routine (ladder file 8).
3. Before and after the Min/max Count Block with the new preset
value is transferred to the 1746-HSCE2, the Counter Control
Block (with the transmit bit reset), is in the 1746-HSCE2’s output
image. Leaving the Counter Control Block in the module’s
output image allows for easy disabling of the counters and
implementing of soft presets.
Programming Blocks Offset 0123456789
Module Setup N10:0 1 101 80000000
Counter Configuration N10:10 302 1C 0 C 000000
Min/Max Count Value Counter 1 N10:20 400230082000
Min/Max Count Value Counter 2 N10:30 104 0 0 7 C8 00000
Min/Max Rate Value N10:408FF9C064000000
Program Ranges N10:50 410 10043E71000
Program Ranges N10:60 410 25093E72000
Program Ranges N10:70 410 4 A 0 E 3E7 1000
Program Ranges N10:80 410 8 F 0 13 3E7 2000
Program Ranges N10:90 410 10 14 0 18 3E7 1000
Program Ranges N10:100 410 20 19 0 1D 3E7 2000
Program Ranges N10:110 410 40 1E 0 22 3E7 1000
Program Ranges N10:120 410 80 23 0 27 3E7 2000
Program Ranges N10:130 110 100 0 0 1 31F 4000
Program Ranges N10:140 110 200 1 320 3 257 8000
Program Ranges N10:150 110 400 3 258 5 18F 4000
Program Ranges N10:160 110 800 5 190 7 C7 8000
Counter Control N10:170 80 8001 8001 0 0 FF00 FFF 0 0 0
Offset 0123456789
N11:0 170 170 17