Publication 1746-UM002B-EN-P - August 2004
4-28 Configuration and Programming
Programming Block Default
Values
The following tables list the default values for all of the programmed
parameters in each class and operating mode. The default operating
mode for each class is mode 1.
Class 1
Figure 4.10 Determining Actual Outputs
Range Bit Setting 11001100
Output ON Mask 00010001
Output Enable Mask 00001111
Actual Outputs 00001101
Table 4.11 Class 1, Mode 1 Default Values
Parameter Counter 1 Counter 2
Debug Mode Selection Inactive
Range Allocation 8 8
Counter Type Ring Ring
Input Configuration X1 Quadrature X1 Quadrature
Gate/Preset Mode Store/Preset/Start Store/Preset/Start
Minimum Count -32,767 -32,767
Maximum Count +32,767 +32,767
Minimum Rate -32,767 -32,767
Maximum Rate +32,767 +32,767
Preset Value 0 0
All Output Ranges Not programmed.
Interrupt Enable Interrupt disabled
Rate Value Format Integer (not programmable)