Publication 1746-UM002B-EN-P - August 2004
Start Up, Operation, Troubleshooting, and Debug Mode 5-3
Module Programming Errors
A programming error is caused by improper set up of a module
parameter. The module responds to a programming error by setting
the programming error bit. When this bit is set, the entire
programming block is rejected.
The programming error bit is set when a reserved bit is set. It is also
set under the following conditions:
Table 5.1 Error Conditions by Programming Block
Programming
Block
Error Conditions
Module Setup Operating mode bits are not set to a valid pattern.
A counter’s range allocation value is greater than 16.
The sum of all range allocation values is greater than 16.
The range allocation value for Counter 2 and/or Counter 3 is
nonzero and the programmed operating mode has the counter
disabled.
A counter or counters were running when the block was sent.
The INT bit was set in Class 1.
The RVF bit was set in Class 1.
Counter
Configuration
Counter number bits are not set to a valid number.
(Operating mode may be incorrect.)
Input configuration is invalid for the counter.
(Operating mode may be incorrect.)
G/P mode is invalid for the counter.
(Operating mode may be incorrect).
The selected counter was running when the block was sent.
The program counter number bits are not set for a counter that
has one or more bits set in its corresponding counter setup
word.
Min./Max.
Count Value
Counter number bits are not set to a valid number. (Operating
Mode may be incorrect.)
The minimum count is outside its valid range.
The maximum count is outside its valid range.
The maximum count is less than or equal to Minimum Count.
Programmed output count ranges are outside the bounds of the
new minimum/maximum count values.
The preset value is outside its valid range.
Counter was running when the minimum/maximum count
value was changed.