Publication 1746-UM002B-EN-P - August 2004
2-2 Module Operation
Input Configurations
Input configurations determine how the A and B inputs cause the
counter to increment or decrement. The six available configurations
are:
Pulse/External Direction
Pulse/Internal Direction
Up and Down Pulses
X1 Quadrature Encoder
X2 Quadrature Encoder
X4 Quadrature Encoder
See the Summary of Available Counter Configurations on page 2-8 for
the input configurations available for the counters, based on operating
mode.
Pulse/External Direction
With this configuration, the B input controls the direction of the
counter, as shown below. If the B input is low (0), the counter
increments on the rising edges of input A. If the input B is high (1),
the counter decrements on the rising edges of input A.
Figure 2.2 Pulse/External Direction Configuration
12321012
Input A
Encoder or Sensor
Count Pulse
Count Pulse
Count
Input B
Input Z
Direction Control
Sensor or Switch
Direction Control
High = Decrement
Low = Increment