Publication 1746-UM002B-EN-P - August 2004
Installation and Wiring 3-7
Input and Output
Connections
Input and output wiring terminals are shown in the figure below.
Each terminal accepts #14 AWG wire. Tighten screws only tight
enough to immobilize the wire. The torque applied to the screw
should not exceed 0.9 Nm (8 in-lb.).
Figure 3.4 Terminal Wiring
Removing the Terminal Block
Remove the terminal block by turning the slotted terminal block
release screws counterclockwise. The screws are attached to the
terminal block, so it will follow as the screws are turned out.
ATTENTION
!
To avoid cracking the removable terminal block,
alternate turning the slotted terminal block release
screws.
B1-
A1-
A2-
Z1-
Z2-
B2-
OUTPUT 2
OUTPUT 0
OUTPUT +Vdc
B1+
A1+
A2+
Z1+
Z2+
B2+
OUTPUT 1
OUTPUT COMMON
OUTPUT 3
Release Screw
Release Screw