Publication 1746-UM002B-EN-P - August 2004
2-10 Module Operation
Ring Counter
Figure 2.6 demonstrates ring counter operation. In ring counter
operation, the count value changes between programmable minimum
and maximum values. If, when counting up, the counter reaches the
maximum value, it rolls over to the minimum value. If, when counting
down, the counter reaches the minimum value, it rolls over to the
maximum value.
Figure 2.6 Ring Counter Diagram
Rate Value
The rate value reported to the processor is calculated in counts per
second (Hz), and is available with all input configurations. The input
configuration determines how the rate value is calculated. When the
count value is increasing, the rate value is positive. When the count
value is decreasing, the rate value is negative.
The rate value is generally calculated as follows:
When the first input pulse is received, the value of an independent,
free-running timer (Ta) is recorded. The module waits approximately
16 ms, while counting more input pulses. After 16 ms, the module
waits for the next input pulse, and the value of the independent timer
(Tb) is again recorded. The module then calculates the rate value
using the formula:
Rollover
Count Up
Count Down
Maximum Value
Minimum Value
rate value
number of counts
Tb Ta
------------------------------------------


=