B-12
DeviceNet Adapter for use with DPI AC Drives
Action that the adapter and drive take if the adapter detects that
DeviceNet communications with a peer have been disrupted. This
setting is effective only if I/O is transmitted through the adapter.
Node address of the node producing the peer I/O.
Important: This parameter can be changed only when Peer Inp
Enable (37) is Off.
34 Peer Flt Action
Range:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Fault Cfg
Default:
0 = Fault
Type:
Read/Write
Reset Required:
No
!
ATTENTION: Peer Flt Action (34) lets you determine
the action of the adapter and connected drive if the
adapter is unable to communicate with the
designated peer. By default, this parameter faults the
drive. You can set this parameter so that the drive
continues to run. Ensure that the setting of this
parameter does not create a hazard of injury or
equipment damage. Failure to observe this
precaution could result in bodily injury or damage to
equipment.
35 Peer Node to Inp
Range:
0 to 63
Default:
0
Type:
Read/Write
Reset Required:
No