C-6
DeviceNet Adapter for use with DPI AC Drives
C.3 Register Object
Class Code
Instances
Class Attributes
Not supported.
Hexadecimal Decimal
0x07 7
Instance Description
1 All polled data being read from the DPI device (read-only)
2 All polled data written to the DPI device (read/write)
3 Logic Status and Feedback data (read-only)
4 Logic Command and Reference data (read/write)
5 Datalink A (input data from device to scanner) (read only)
6 Datalink A (output data from scanner to device) (read/write)
7 Datalink B (input data from device to scanner) (read only)
8 Datalink B (output data from scanner to device) (read/write)
9 Datalink C (input data from device to scanner) (read only)
10 Datalink C (output data from scanner to device) (read/write)
11 Datalink D (input data from device to scanner) (read only)
12 Datalink D (output data from scanner to device) (read/write)
13 Logic Status and Feedback Data (read-only)
14
Mask
1
(read/write)
1
The mask command word is set to the value of the first word of the data
where there are ones in the second word of the data. Command = (word
1 and not word 2) or (word 1 and word 2). This only controls specified bits
in the Logic Command data to the DPI product and does not change the
Reference value.