Rockwell-automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Manual de usuario Pagina 88

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 168
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 87
8-8
DeviceNet Adapter for use with DPI AC Drives
6 EEPROM
Sum Flt
The EEPROM in the adapter is corrupt.
7Online @
125 kbps
The adapter and DPI product are communicating at
125 kbps.
8Online @
500 kbps
The adapter and DPI product are communicating at
500 kbps.
9 Bad Host Flt The adapter was connected to an incompatible
product.
10 Dup. Port Flt Another peripheral with the same port number is
already in use.
11 Type 0 Login The adapter has logged in for type 0 control.
12 Type 0 Time
Flt
The adapter has not received a type 0 status
message within the specified time.
13 DL Login The adapter has logged into a Datalink.
14 DL Reject Flt The host rejected an attempt to log in to a Datalink
because the Datalink is not supported or is used by
another peripheral.
15 DL Time Flt The adapter has not received a Datalink message
within the specified time.
16 Control
Disabled
The adapter has sent a “Soft Control Disable”
command to the DPI product.
17 Control
Enabled
The adapter has sent a “Soft Control Enable”
command to the DPI product.
18 PCCC IO Time
Flt
The adapter has not received a PCCC control
message within the specified time-out interval.
19 Normal
Startup
The adapter successfully started up.
20 Message
Timeout
A client-server message sent by the peripheral was
not completed.
21 DPI Fault Msg The DPI Host has faulted.
22 DN Poll
Timeout
A polled I/O connection has timed out.
23 DN I/O Too
Long
Reconfigure the I/O length in the scanner.
24 Bad I/O
Fragment
A DeviceNet I/O fragment was received out of
sequence. Possible line noise problem.
Table 8.5 – Event Codes and Descriptions (Continued)
Code Event Description
Vista de pagina 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 167 168

Comentarios a estos manuales