Vista de pagina 126
DeviceNet Objects
C-19
C.8 DPI Parameter Object
Class Code
Instances
The number of instances depends on the number of parameters in
the device. The total number of parameters can be read in
Instance 0, Attribute 0.
Class Attributes
Hexadecimal Decimal
0x93 147
Number Description
0 Class Attributes (Drive)
1 Drive Parameter 1 Attributes
2 Drive Parameter 2 Attributes
16384 Class Attributes (Adapter)
16385 Adapter Parameter 1 Attributes
Attribute
ID
Access
Rule Name
Data
Type Description
0 Get Number of
Instances
WORD Number of parameters in the
device
1 Get/Set Write Protect
Password
WORD 0 = Password disabled
n = Password
2 Set NVS
Command
Write
BYTE 0 = No operation
1 = Store values in active memory
to NVS
2 = Load values in NVS to active
memory
3 = Load default values to active
memory
3 Get NVS
Parameter
Value
Checksum
WORD Checksum of all parameter values
in a user set in NVS
4 Get NVS Link
Value
Checksum
WORD Checksum of parameter links in a
user set in NVS.
Vista de pagina 126