8 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 1 Overview of the 1734 POINT and 1738 ArmorPOINT EtherNet/IP Adapters
Rack-optimized connections reduce the total number of connections needed to
transfer data when using many digital I/O modules in a system. The following
example illustrates the benefit of rack-optimized connections.
Assume you set up a system that contains eight digital I/O modules interfaced to
an adapter. If you use direct connections to transfer data to each of the these I/O
modules, you need eight connections to transfer all of the data, one to each of the
eight I/O modules. If you use a rack-optimized connection to transfer the data,
you only need a single connection – the connection to the I/O adapter.
See the EtherNet/IP Embedded Switch Technology Application Guide,
publication ENET-AP005
, for more information on connections.
Mixing Rack-optimized and Direct Connections
You can mix communication formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter. I/O modules
configured for direct communication communicate at their own individual RPIs
and ignore the rack-optimized RPI.
Chapter Summary
In this chapter, you were introduced to the features of the POINT I/O and
ArmorPOINT I/O Adapters, and considerations for installation and usage.
IMPORTANT
Although rack-optimized connections offer an efficient way to use
resources, there are a few limitations on their use:
You can use only rack-optimized connections to send data to and
from digital I/O modules. Analog or speciality I/O requires direct
connections.
All data is sent at the same time as the RPI rate of the I/O adapters.
If the update rate required for a digital module is different from the
RPI of the rack-optimized connection, a direct connection to that
digital I/O module is required.