30 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Set Up the Hardware
The following section describes how to set up the I/O Hardware.
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3. The 1734-AENTR/B adapter is mounted
on a DIN rail in slot 0, with a 1734-OW2/C relay output module in slot 1, a
1734-OV4E/C sink output module in slot 2, and a power supply (not shown).
To work along with this example, set up your system as shown in the figure.
In the example application, we assume that the L63 controller and
1756-ENBT module (firmware revision 2.3, or later) are in the slots shown
in the figure.
Verify the IP addresses for your programming terminal, 1756-ENBT
module, and adapter.
Verify the position (slot) of the I/O modules on the DIN rail.
Verify that you connected all wiring and cabling properly.
Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software, as described in
Appendix C
in this manual.
Local
chassis
POINT I/O
L63
controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Data
Switch
10.88.70.26
Programming
terminal
Slot 0 1 2 3
1734-AENTR
10.88.70.2
Slot 0 1 2 3 4
02
0
1734-AENTR Series B
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
Link 1
Activity/
Status
Link 2
Activity/
Status
IP ADDRESS
45176