Rockwell-automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Manual de usuario Pagina 71

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 120
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 70
Rockwell Automation Publication 1734-UM017B-EN-P - October 2013 63
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
9. In the New Module screen select the Connection Tab.
10. Verify that the Requested Packet Interval (RPI) used for the rack-
optimized connection to the I/O modules is appropriate for your system
(20.0 ms for this example). If not, change it to the correct value.
11. Click OK to accept the configuration.
The 1734-AENTR/B adapter appears indented under the local
1756-ENBT bridge module in the I/O Configuration folder.
IMPORTANT
To avoid overloading the adapter, it is recommended that the RPI be
no less than 10.0 ms for rack connections and 50.0 ms for direct
connections.
Vista de pagina 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 119 120

Comentarios a estos manuales

Sin comentarios