Rockwell-automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Manual de usuario Pagina 59

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 120
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 58
Rockwell Automation Publication 1734-UM017B-EN-P - October 2013 51
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Configure the Adapter with
Fixed IP Address
To configure the adapter with a fixed IP address to prevent the adapter from
ceasing to communicate with the ControlLogix controller:
1. All controllers with I/O connections to the AENTR and/or the modules
in its backplane need to be in program mode.
2. In the Module Properties dialog, click the Internet Protocol tab.
3. If it is not selected, select Manually configure IP settings.
4. Enter values for Physical Module IP Address, and Subnet Mask, noting we
used the following values:
5. Click Set
6. Read and acknowledge the warning.
7. Click OK.
8. Click the Refresh communication button to verify the changes.
Physical Module IP Address 192.168.1.29
Subnet Mask 255.255.255.0
Vista de pagina 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 119 120

Comentarios a estos manuales

Sin comentarios