44 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
4. Enter values for Name and Slot, noting that we used the following values.
5. Choose the Connection tab to set the RPI value.
RPI is selectable since it is a direct connection.
Note that the RPI is selectable and has a default value. Because we are
making a direct connection to each I/O module, we must specify an RPI to
determine how often the data is exchanged with the 1738-AENT adapter
for each module.
6. Enter 10 ms as the RPI for the 1734-OV4E module.
Name POINT_Digital_Output
Slot 2
IMPORTANT
To avoid overloading the I/O adapters, we recommend that RPI be no
less than 10 ms for rack connections and 50 ms for direct
connections.