74 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Access Module Data
Use the following information to use the I/O adapter data in the ladder logic
program:
POINT_IO_Adapter — the name you gave to your EtherNet adapter
# — slot number of POINT I/O module
C — configuration, I = input, O = output
Use the controller tags in your ladder program to read input data or write output
data.
For ControlLogix controller information, refer to ControlLogix System
User Manual, publication 1756-UM001
.
Slot Status Bits: The Slot Status bits display the connection status for each
of the POINT I/O modules that use a rack-optimized connection.
Bit 0 is reserved for the adapter and always reports a value of 1.
Each of the other bits (1 to 63) correspond to a POINT I/O module
that you install in the POINT I/O backplane.
In this example, we configured the 1734-AENTR adapter for both
rack-optimized and direct connections.
The slot status bits indicate that we installed the module in slot 2 with it
operating correctly:
0 = module participating with no errors and
1 = module not participating or connection error (typically, module
removed/missing)
Chapter Summary
This chapter provided instructions on configuring an AENTR Adapter for
Direct Connection and Rack Optimization in RSLogix 5000 Software. It
included information about hardware setup; configuring the I/O Modules;
adding an I/O adapter to the I/O configuration; configuring for rack-optimized
connections; configuring for direct connections; and accessing module data.