114 Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 5 Diagnostics and Troubleshooting
Module Error Definition
Module errors are expressed in two fields as four-digit Hex format, with the most
significant digit as ‘dont care’ and irrelevant. The two fields are ‘Module Error
and ‘Extended Error Information. The structure of the module error data is
shown in
Table 19.
Module Error Field
The purpose of the module error field is to classify module errors into three
distinct groups, as described in
Table 20. The type of error determines what kind
of information exists in the extended error information field. These types of
module errors are typically reported in the controllers I/O status file. Refer to
your controller manual for details.
Extended Error Information Field
Check the extended error information field when a non-zero value is present in
the module error field. Depending upon the value in the module error field, the
extended error information field can contain error codes that are module-specific
or common to all 1769 modules.
Hardware Errors
General or module-specific hardware errors are indicated by module error code 1.
See the
General Common Hardware Error Codes table on page 116 for more
information.
Table 19 - Module Error Definition
‘Don’t Care’ Bits Module Error Extended Error Information
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0000000000000000
Hex Digit 4 Hex Digit 3 Hex Digit 2 Hex Digit 1
Table 20 - Module Error Types
Error Type Module Error Field Value Bits
11 through 09 (Binary)
Description
No Errors 000 No error is present. The extended error field holds no additional information.
Hardware Errors 001 General and specific hardware error codes are specified in the extended error
information field.
Configuration Errors 010 Module-specific error codes are indicated in the extended error field. These error codes
correspond to options that you can change directly. For example, the input range or input
filter selection.
TIP
If no errors are present in the module error field, the extended error
information field will be set to zero.