Program a 1769-HSC Module, MicroLogix 1500 Controller, and 845F Incremental Encoder with RSLogix 500 Software Appendix C
Configure Your 1769-HSC
Module
You configure the 1769-HSC module in an offline project and then download to
the MicroLogix 1500 controller.
1. To open the 1769-HSC-module configuration file, click Adv Config.
2. To display the counter configuration information with the default values,
click the Counters Tab.
3. Use this information to complete the configuration for the Counters tab.
Option Value
# of Counters 2 (default)
Counter 1 contents must be cleared to store
changes if the number of counters is
changed to 1.
Operational Mode (Quadrature) Encoder X 4
Max Count 1,200,000
Min Count 0
Preset 1
Update Time 1
Count Behavior on Configuration Retained
Hysteresis: 0
RPM Scale Factor 1
Storage Mode All unchecked
Acc behavior Over/Under Flow Ring Counter
Filters (A, B, Z ) None