Rockwell Automation Publication 1769-UM006E-EN-P - July 2013 139
Program a 1769-HSC Module, CompactLogix Controller, and 845F Incremental Encoder with RSLogix 5000 Software Appendix B
11. In the Controller Organizer, double-click Controller Tags.
12. At the bottom of the window, click Monitor Tags.
The tags for I/O modules appear in the following format, where ‘s’ is the
slot number of the module.
13. Click ‘+’ to expand the output tags (Local:4:0).
14. Use this information to configure these output tags.
Your output tags should look like the example.
Tag Description
Local:s:I Input Image
Local:s:O Output Image
Local:s:C Configuration Data
Tag Value
OutputOnMask 2#0000_0000_0000_0000
OutputOffMask 2#0000_0000_0000_0011
RangeEn 2#0000_0000_0000_0011
ResetBlownFuse 0
Ctr0 2#0000_0000_0000_0001
(1)
(1) Changing this bit to a 1 changes the CtrOEn tag to 1 when you press Tab.