5-43 Specifications
Publication 198-UM002A-EN-P December 2001
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
Input 1 represents the disconnect status of the distributed starter. Input 2 represents the contactor feedback
of the preset speed module. If this bit is set, the disconnect or contactor is closed. If this bit is not set, the
disconnect or contactor is open.
Figure 5.30 Cat. No. 198-IB2XOB1 Typical Wiring
Table 5.28 Cat. No. 198-IB2XOB1 I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
——————Input2 Input 1
Input Data — Assembly Instance 101
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
——Input2 Input 1
Output Data — Assembly Instance 102, 104, or 106
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
———————Output1
Output Data — Assembly Instance 100
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
———Output1
Typical Wiring Series A Typical Wiring Series B
IN1
IN2
Out A
+Vout
+V
0V
Input 2
Output 1
Input 1
0V
0V
+V
Out A
In2
In1
+Vout
24V DC