5-63 Specifications
Publication 198-UM002A-EN-P December 2001
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
When wired as shown in the following diagrams. Typical in a Distributed Starter. Input 1 represents the
disconnect status. Input 2 represents the fault status of the 160 drive.
Table 5.34 198-IB2XOB2S-Q5 I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1 Bit 0
——————Input2 Input 1
Input Data — Assembly Instance 101
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
——Input2 Input 1
Output Data — Assembly Instance 100
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
Run Reverse Run Forward
Output Data — Assembly Instance 102, 104, or 106
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1 Bit 0
——————Run ReverseRun
Forward
Drive Control
Run
Reverse
Run
Forward
Drive
Control
Run
Reverse
Run
Forward
Drive
Control
00Stop 10Run Reverse
0 1 Run Forward 1 1 Stop